Page 15
MMM DD, YYYY HH:MM XM
T1: SUDDEN LOSS ALARM
MMM DD, YYYY HH:MM XM
T1: HIGH PRODUCT ALARM
(Flashing Yellow light)
(Flashing Red light)
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
T1: MAX PRODUCT ALARM
(Flashing Red light)
MMM DD, YYYY HH:MM XM
T1: PROBE OUT ALARM
(Flashing Red light)
ALARM
TEST
ALARM
TEST
CAUSE:
Fuel loss in the tank has exceeded a 
pre-set limit during a Leak Test. This 
indicates a possible leak, fuel being 
dispensed or other unauthorized loss.
ACTION: 
Check that fuel has not been 
dispensed from the tank during the 
test period. Contact your VR Service 
Contractor for advice.
CAUSE:
Fuel level in the tank has exceeded 
the High Product Alarm limit.
ACTION:
Stop the delivery immediately!
CAUSE:
Fuel level in the tank has exceeded 
the Safe Working Capacity.
ACTION: 
Stop the delivery immediately!
CAUSE:
There is a fault with the sensing 
probe in the tank.
ACTION:
Contact your VR Service Contractor 
for advice.
In-Tank Alarms (Continued)