In-Tank Alarms (Continued)
(Flashing Red light)
ALARM
TEST
(Flashing Red light)
ALARM
TEST
MMM DD, YYYY HH:MM XM
T1: PER TST NEEDED ALM
MMM DD, YYYY HH:MM XM
T1: PERIODIC TEST FAIL
(Flashing Red light)
ALARM
TEST
(Flashing Red light)
ALARM
TEST
MMM DD, YYYY HH:MM XM
T1: ANN TST NEEDED ALM
MMM DD, YYYY HH:MM XM
T1: ANNUAL TEST FAIL
CAUSE:
A periodic in-tank leak test has not
been successfully completed within
the preset time period.
ACTION:
Schedule a 0.2 gph (0.76 lph) test.
CAUSE:
An annual in-tank leak test has not
been successfully completed
within the preset time period.
ACTION:
Schedule a 0.1 gph (0.38 lph) test.
CAUSE:
In-tank leak periodic (0.2 gph [0.76 lph])
test failed.
ACTION:
Rerun in-tank leak test. If second test
fails, contact your VR Service Contrac-
tor for advice.
CAUSE:
In-tank leak annual (0.1 gph [0.38
lph]) test failed.
ACTION:
Rerun in-tank leak test. If second
test fails, contact your VR Service
Contractor for advice.