TLS-350 Series Sensor Module Installation Guide Connecting Sensor Wiring to Modules
7
Figure 4. Interstitial Sensor Interface Module Wiring Diagram
TYPE B, VAPOR SENSOR, & GROUNDWATER SENSOR MODULES
For Type B, Vapor Sensor, and Groundwater Sensor Interface Modules, connect the three marked or color-coded
wires from each sensor to the appropriate terminals (see Figure 5, Figure 6, and Figure 7 on page 8):
Figure 5. Type B Interface Module Wiring Diagram
SENSOR
MAXIMUM SENSOR
OUTPUT RATINGS:
15 VDC
.15 AMP
+ + + + + + + +
1 2 3 4 5 6 7 8
INTERSTITIAL SENSOR INTERFACE MODULE
consoles\isimw.eps
Sensor
#2
Sensor
#1
Up to 8 sensors
Console
Sensor
#8
Attach Cable Shields to Ground
Lug Closest to Conduit Entry
Rigid Conduit
(enters Console
through an I.S. Bay
knockout)
SENSOR
MAXIMUM
SENSOR
OUTPUT
RATINGS:
13 VDC
.20 AMP
AGB AGBAGBAGBAGB
TYPE B INTERFACE MODULE
1 2 3 4
5
AGB
6
consoles\tbimw.eps
Console
Up to 6
Sensors
Sensor
#1
Sensor
#2
Sensor
#6
ABGABGABG
Attach Cable Shields to Ground
Lug Closest to Conduit Entry
Rigid Conduit
(enters Console
through an I.S. Bay
knockout)