5-4
5 Warning and Alarm Messages Displayed Alarm Messages
Fuel Quality Alarm Water/phase separation may be pres-
ent in tank.
Test fuel at bottom of tank to ensure
water/phase separation is not present.
Gross Leak Test Fail Alarm In-tank leak (3.0 gph [11.3 lph]) test
failed.
Rerun in-tank leak test. If second test
fails, call for service.
High Product Alarm Product level in tank rose above pro-
grammed limit.
Do not allow additional delivery until
product is dispensed below preset limit.
High Water Alarm Water detected in tank exceeds pro-
grammed alarm limit.
Remove water from tank.
High Water Warning Water detected in tank exceeds pro-
grammed warning limit.
Remove water from tank.
Invalid Fuel Level Alarm Product level is too low, causing the
fuel and water floats to be too close
together.
Call for a delivery.
Leak Alarm A static in-tank leak test failed.Rerun
in-tank leak test.
Rerun in-tank leak test.
Leak Test Active In-tank leak test is underway. Do not dispense fuel from this tank until
message disappears.
Low Product Alarm Tank level dropped below the pro-
grammed limit.
Call for a delivery.
Maximum Product Alarm Product level rose above the pro-
grammed limit.
Stop delivery. Do not allow additional
delivery until product drops below preset
limit.
Missing Delivery Ticket Warning Delivery Ticket information has not
been entered at the console.
Enter Delivery Ticket information.
No CSLD Idle Time Warning System has not had enough idle time
over previous 24 hours to run a statis-
tical leak detection test.
Stop dispensing fuel from this tank until
CSLD test is complete.
Overfill Alarm Fuel level has exceeded a pro-
grammed limit. Potential overflow of
tank may occur.
Stop delivery. Check for spillage.
Periodic Leak Test Fail Alarm In-tank leak (0.2 gph [0.76 lph]) test
failed. Dispensing halts if pro-
grammed to do so.
Rerun in-tank leak test. If second test
fails, call for service.
Periodic Test Needed Alarm A periodic in-tank leak (0.2 gph [0.76
lph]) test has not been successfully
completed within the programmed
number of days.
Schedule a 0.2 gph (0.76 lph) test.
Periodic Test Needed Warning A periodic in-tank leak (0.2 gph [0.76
lph]) test has not been successfully
completed within the programmed
number of days.
Schedule a 0.2 gph (0.76 lph) test.
Probe Out Alarm Hardware failure - probe or intercon-
necting wiring to console.
Call for service following the procedures
established for your site.
Setup Data Warning Device setup data problem. Recheck device setup parameters.
Table 5-2. Tank Alarms
Alarm Cause Action