PMC Alarm Diagnostics for ISD/PMC and PMC Only Configurations
PMC SETUP
Incomplete PMC Setup requirements
ISD MONITORING CATEGORY
ISD Setup Diagnostic self-tests (ref. page 17) are designed to monitor and ensure proper monitor configuration.
Setup self-test will verify that the Pressure Management Control is configured.
VST ECS MEMBRANE / VST GREEN MACHINE DIAGNOSTIC PROCEDURE
No
No
No
No
Did PMC SETUP FAIL
alarm clear?
Contact Veeder-Root
Technical Support
Yes
Correct the condition.
MODE out of the Setup
Menu.
Press the ALARM key.
Check if alarm cleared.
1.
2.
3.
4.
More than one
Relay assigned to
the vapor
processor?
Yes
Yes
Yes
Relay Configured,
Enabled and
assigned to the
vapor processor?
No
No
Yes
Is a Hydrocarbon
Sensor selected
in PMC Setup?
Vapor Pressure
Sensor installed and
configured?
Gasoline tank
installed and
configured?
Yes
No
START
Complete