PMC Alarm Diagnostics for ISD/PMC and PMC Only Configurations PMC SETUP
26
V-R VAPOR POLISHER DIAGNOSTIC PROCEDURE
No
No
No
Yes
Did PMC SETUP FAIL
alarm clear?
Contact Veeder-Root
Technical Support
Yes
Correct the condition.
MODE out of the Setup
Menu.
Press the ALARM key.
Check if alarm cleared.
1.
2.
3.
4.
Vapor Valve
Installed.
Configured and
Enabled?
Yes
Yes
Yes
ATM Sensor
Configured and
Enabled?
No
No
No
7 Sensor Input
module
installed?
Vapor Pressure
Sensor installed and
configured?
Gasoline tank
installed and
configured?
Yes
START
Complete
No