l With pressure, displayed value "Pressure" or "Height"
means: presentation of the measured value in the selected
adjustment unit, e.g. bar or m.
Displayed value
Scaled
Anzeigeeinheit
Volumen
l
Scaling
0 %=0.0 l
100 %=100.0 l
Menu section, service
In the menu item "Current output" you determine the behaviour
of the current output during operation and in case of failure.
The following options are available:
Current output
Output mode
4 20 mA
20 4 mA
Failure mode
4)
Hold value
20.5 mA
22 mA
<3.6 mA
Min. current
5)
3.8 mA
4 mA
Max. current
6)
20 mA
20.5 mA
The values in bold font represent the data of the factory setting.
In HART multidrop mode, the current is constantly 4 mA. This
value does not change even in case of failure.
4)
Value of the current output in case of failure, e.g. if no valid measured value
is delivered.
5)
This value is not underrun during operation.
6)
This value is not exceeded during operation.
Current output
22 Indicating and adjustment module PLICSCOM