12
MINI DOGE / MINI DOGE L
TERMINAL CONNECTIONS
TERMINAL CONNECTION
1
Trigger (positive = activated) of the LED devoted to the notice of the alarm system status
(alarm system armed/disarmed) - on L Model only
2
Independent trigger of the LED flashing unit for alarm optical notice (positive = activated)
- see DIP 1, L Model only
3
Sound 1 (positive = activated) command (DIP 4 = OFF) - sound 4 command (DIP 4 = ON)
3 & 4
Sound 7 (positive = activated) command (DIP 4 = OFF) - sound 4 command (DIP 4 = ON)
4
Sound 2 (positive = activated) command (DIP 4 = OFF) - sound 5 command (DIP 4 = ON)
4 & 5
Sound 8 (positive = activated) command (DIP 4 = OFF) - sound 5 command (DIP 4 = ON)
5
Sound 3 (positive = activated) command (DIP 4 = OFF) - sound 6 command (DIP 4 = ON)
6
Free terminal
7
0 Vdc – Ground
8
Tamper (connect to the tamper line coming from the control panel)
9
Tamper (connect to the tamper line coming from the control panel)
ATTENTION: give power supply to the sounder using a control panel output with SELV
voltage and limited power.
DIP-SWITCHES SETTING
DIP 1 – FLASHING UNIT SELECTION (L model)
OFF
The flashing unit follows the alarm trigger (default setting)
ON
The flashing unit follows the separated flashing unit trigger - terminal no. 2
DIP 2 – OFF (DO NOT MODIFY)
DIP 3 – OFF (DO NOT MODIFY)
DIP 4 – SOUND SELECTION
OFF
Sound 1 Modulated alarm – terminal no. 3
Sound 2 Venitem modulated alarm – terminal no. 4
Sound 3 Pre-alarm softened intermittent – terminal no. 5
Sound 7 Modulated alarm – terminals no. 3 and 4
Sound 8 Pulsed fast alarm – terminals no. 4 and 5
(default setting)
ON
Sound 4 Bi-tone immediate evacuation alarm – terminal no. 3 or 3 + 4
Sound 5 Fixed frequency continuous evacuation alarm– terminal no. 4 or 4 + 5
Sound 6 Pulsed intermittent pre-alarm sound for evacuation – terminal no. 5