Modification TR (Fig. 76):
Ò1 - turn-on delay time can be set from 0 to 150 seconds;
Ò - turn-off delay can be set from 2 to 30 minutes.
Modification I (Fig. 77):
Ò - interval timer can be set within the range from 30 minutes to 15 hours.
Modification F (Fig. 77):
Ò - turn-off delay can be set from 2 to 30 minutes.
Modification H (Fig. 78):
Ò - turn-off delay can be set from 2 to 30 minutes.
H - humidity sensor threshold can be set within the range from 60% to 90%.