4. Installation / Commissioning
4.1. Installation Instructions
Note: Installation of this equipment should only be carried out by a suitable qualified person.
4.1.1. General Installation Information
· A minimum of 50mm clearance is required at the back
of the machine. This allows for access to the water
inlet and electrical connection at the rear of the
machine.
· A minimum of 150mm clearance is required either
side of the Compact. This allows tool access during
adding/removing of the front panel. Servicing and
maintenance procedures may also be carried out
without having to move the machine.
150mm 150mm
50mm
350mm
SIDE & REAR MACHINE CLEARENCE
LID CLEARENCE & MACHINE HEIGHT
· A minimum of 350mm clearance is required above the
Compact lid. Items fitted to the wall directly above the
machine may restrict the lid from opening and
operating effectively.
· For the foot sensor to operate the machine MUST
measure between 220 & 250mm from the floor to the
sensor as shown, this is the effective operation range
of the ultrasonic sensor.
· If there are circumstances preventing the machine
from being fitted at this height it may be possible to
have a service engineer teach the sensor a new
nominal position, however this should be avoided if
possible.
Between 220 – 250mm