4.4 Commissioning Record List
The commissioning record is given in the Table 4.1 below for user reference.
Form Test Items Inspection Standards Result Test Items Inspection Standards Result
Battery
module
Battery module
indicators
Normal Display status
Each item shows compliance with
requirements.
Control
section
Display
operating
conditions
No scrolling, messy screen
Battery
information
display
Normal display
System
parameters
Setting is correct
Time display Timing is correct. Address settings The address is correct.
Contactor status Closed and normal
Battery charge
and discharge
Current discharge is negative, charge
is positive, charge/discharge state is
correct.
AC start AC start normal DC start DC start normal
Temperature
and humidity
display
Data is normal and
recorded
Environmental
humidity
Data is normal and recorded
Cluster
voltage
difference
Module 1 total
voltage
Pressure difference with
other modules less than
10 V.
Module 5 total
voltage
Pressure difference with other
modules less than 10 V.
Module 2 total
voltage
Pressure difference with
other modules less than
10 V.
Module 6 total
voltage
Pressure difference with other
modules less than 10 V.
Module 3 total
voltage
Pressure difference with
other modules less than
10 V.
Module 7 total
voltage
Pressure difference with other
modules less than 10 V.
Module 4 total
voltage
Pressure difference with
other modules less than
10 V.
Module 8 total
voltage
Pressure difference with other
modules less than 10 V.
Battery
parameter
logging
Maximum cell
voltage
Record
Maximum cell
voltage
Record
Maximum cell
temperature
Record
Maximum cell
temperature
Record
Table 4.1 Reference Commissioning Record List