9.7 Air Cooled Condenser Maintenance
Restricted airflow will reduce operating efficiency and could result in high compressor head pressure and loss of cooling.
Clear the coil surface of all debris that will inhibit airflow.
Check for bent or damaged coil fins and correct.
Do not permit snow to accumulate around or under the outdoor unit.
Periodically consider commercial cleaning of the coil surface
Inspect fans, motors and controls for proper operation.
Check all piping and capillaries for proper support.
Inspect for leaks.
Check contactors for pitting. Replace if pitted.