Liebert® MCV
Installer/User Guide
60 Hz and 50 Hz, High Density Microchannel Condenser

Table of Contents

Questions and Answers

  • J
    Jose SmithAug 17, 2025
    How to troubleshoot high discharge pressure in Vertiv Industrial Equipment?
    • S
      Steven GarzaAug 18, 2025
      To troubleshoot high discharge pressure in your Vertiv Industrial Equipment, start by cleaning the condenser coil. If that doesn't solve the issue, check if the condenser fans are operating correctly by looking for a low voltage signal from the indoor unit and inspecting the fan motors and fuses. Also, verify the refrigerant charge, as a high charge can cause this problem.
  • J
    Julie RamirezAug 20, 2025
    What to do if the condenser will not start in Vertiv Liebert MCV330?
    • E
      Erica HarmonAug 20, 2025
      If the condenser of your Vertiv Industrial Equipment won't start, begin by checking the voltage at the input terminal block to ensure there's power. Also, inspect the condenser electrical panel for tripped circuit breakers or fuses for the low voltage transformer and repair if necessary. Finally, check for an open circuit in the low voltage signal to/from the indoor unit and repair it.
  • C
    clayallisonAug 23, 2025
    Why are the SPD green and red LEDs extinguished on my Vertiv Liebert MCV330?
    • H
      hcoxAug 23, 2025
      If the green and red LEDs on the SPD of your Vertiv Industrial Equipment are off, first check the voltage at the input terminal block to ensure proper voltage and phasing. Then, inspect the electrical connections to the SPD for any faults and repair them. Finally, ensure that the condenser disconnect switch is in the On position and recheck the lights.
  • I
    Isaac AdamsAug 26, 2025
    What to do if the control board LEDs do not light on Vertiv Liebert MCV330 Industrial Equipment?
    • J
      juarezcarolineAug 26, 2025
      If the control board LEDs on your Vertiv Industrial Equipment do not light, check the connection to P24 to ensure it is securely connected. Also, check the connector from the transformer for loose terminals. Verify that the fuses next to P24 have not blown and replace them if needed. Use a voltmeter to verify that the output from the transformer is 24Vac ±10%. If the value exceeds ±10%, verify that the correct primary leads are being used. If there is no output voltage, verify that the primary connections are secure and receiving the correct voltage. If they are, replace the transformer.
  • O
    opattersonAug 28, 2025
    Why will the fan not run on my Vertiv Liebert MCV330 Industrial Equipment?
    • M
      Michael JamesAug 28, 2025
      If the fan of your Vertiv Industrial Equipment will not run, make sure a jumper is installed in the fans if the schematic indicates it's needed based on the fan supplier. Check the wiring at each of the fans to ensure the communication cable connections are secure and correct. Use the parameter list label on the door to find the correct fan parameters and verify that the fan has the correct manufacturer and address selected.
  • E
    Emily SmithAug 30, 2025
    What does it mean when the SPD red LED is illuminated on Vertiv Industrial Equipment?
    • K
      Kayla BennettAug 30, 2025
      If the red LED is illuminated on the SPD of your Vertiv Industrial Equipment, it means a surge exceeding the SPD's rating has occurred. Replace the SPD and inspect other components for damage, replacing them as necessary.
  • C
    cindyellisSep 1, 2025
    What causes low discharge pressure in Vertiv Industrial Equipment?
    • S
      Stacey LevySep 1, 2025
      If you are experiencing low discharge pressure in your Vertiv Industrial Equipment, the issue might be a faulty head pressure control valve or premium efficiency control board. If either of these components is defective, replace it.
  • Q
    qflowersSep 4, 2025
    Why is the discharge pressure high in my Vertiv Industrial Equipment?
    • W
      walterslauraSep 4, 2025
      High discharge pressure in your Vertiv Industrial Equipment can be caused by several factors: * Dirty condenser fins: Clean the coil. * Condenser fans not operating: Check for a low-voltage signal from the indoor unit. Also, check the fan motors and fuses. * High refrigerant charge: Verify the refrigerant charge.
  • S
    Susan GilbertSep 6, 2025
    How to troubleshoot a Vertiv Industrial Equipment condenser that won't start?
    • R
      robertwestSep 6, 2025
      If your Vertiv Industrial Equipment condenser won't start, consider these potential causes and solutions: 1. No power to the condenser: Check the voltage at the input terminal block. 2. Circuit breaker or fuse tripped: Locate the problem in the condenser's electrical panel and repair it. 3. No low-voltage signal: Find the open circuit and repair it.
  • T
    tammieperezSep 9, 2025
    What to do if SPD green and red LEDs are extinguished on Vertiv Industrial Equipment?
    • K
      Keith HaleSep 9, 2025
      If both the green and red LEDs on your Vertiv Industrial Equipment's SPD are off, it could be due to: * No voltage or improper phasing: Check the voltage at the input terminal block. * Faulty electrical connections: Locate and repair any connection problems to the SPD. * Condenser disconnect is turned Off: Turn the disconnect switch to the On position and recheck the lights.

Summary

1 Important Safety Instructions

2 Nomenclature and Components

2.3 Product Description and Features

Describes the MCV condenser as an air-cooled heat rejection unit.

3 Pre-installation Preparation and Guidelines

4 Equipment Inspection and Handling

5 Piping

5.1 Refrigerant Piping and Charging

Guidelines and warnings for refrigerant piping and system charging.

6 Electrical Connections

6.2 Wye vs. Delta Connected Power Supply for EC Fans

Details acceptable and unacceptable power supply configurations.

7 Checklist for Completed Installation

8 Initial Start-up Checks and Commissioning Procedure for Warranty Inspection

9 Troubleshooting

10 Control Operation

10.1 Vertiv Liebert EconoPhase Pumped Refrigerant Economizer with a Vertiv Liebert DSE System

Explains EconoPhase systems for precision air conditioning and energy savings.

10.3 Vertiv Liebert EconoPhase Operation

Describes how EconoPhase operation controls temperature based on outdoor conditions.

11 Maintenance

11.2 Condenser Cleaning - Standard Coil

Guidelines for cleaning standard condenser coils for efficiency.

11.3 Condenser Cleaning - E-coat Coil

Procedures for quarterly cleaning of E-coat coils and cabinets.

11.4 Replacing the Condenser EC Fan

Step-by-step instructions for replacing a condenser EC fan.

11.5 Replacing the Premium Efficiency Control Board

Steps to replace the premium efficiency control board.

12 Preventive Maintenance Checklist

Vertiv Liebert MCV330 Specifications

General IconGeneral
Power Rating330 kVA
Input Voltage400V
Voltage400V
Frequency50/60 Hz
Phase3
TopologyDouble Conversion
TypeUninterruptible Power Supply (UPS)
Output Voltage400V
Communication InterfacesModbus, USB
Operating Temperature Range0°C to 40°C

Related product manuals