greater than the alarm temperature. Check whether the
cabinet temperature probe is connected and placed
correctly, or the compressor and other components are
functioning correctly.
Error code E01 (except BF100)
If the motherboard and display panel lose connection, the
panel will display E01. Power off the appliance, wait 2
minutes, then restart it. If the issue persists, perform a Factory
Reset (below).
Factory Reset
While in work preparation mode, press and hold the +/-
button for 3 seconds until the temperature and time bar
displays "rS" at the same time. Shortly after this display occurs,
the unit will automatically shut down. Press the Power button
to boot and restore the device to the factory settings.
The factory parameters are as follows:
Temperature unit: ℃
Set temperature value: -18 °C
Set time: 4:00
If the E01 code persists or a fault not mentioned above
occurs, contact Vesta Technical Support.
Operating Considerations
• In order to extend the life of the compressor, it should not
be started frequently over short time spans. To protect
the compressor, it will delay start 2 minutes after the
STOP/START button is pressed to start the desired
program. The evaporator fan will start 2 minutes after the
compressor.