List of Property Value Range Restrictions for AI and AV objects
Object name
Object Type
and instance
Under range
value
Over range
value
Default value
Room Temperature AV 7 -40°F (-40°C) 122°F (50°C) N/A
Outdoor Temperature AV 9 -40°F (-40°C) 122°F (50°C) N/A
Room Humidity AV 11 0% 100% N/A
Supply Temp AI 16 -40°F (-40°C) 122°F (50°C) N/A
Supply RH AV 17 0% 100% N/A
Water Temperature AV 17 -40°F (-40°C) 122°F (50°C) N/A
PI Heating Demand AV 20 0% 100% N/A
PI Cooling Demand AV 21 0% 100% N/A
Economizer Output AV 22 0% 100% N/A
AI1 Value AI 23 0 VDC 10 VDC N/A
Analog Heat Output AV 35 0% 100% N/A
Occupied Heat Setpoint AV 42 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Occupied Cool Setpoint AV 43 54°F (12°C) 100°F (37.5°C) 75°F (24°C)
Unoccupied Heat Setpoint AV 44 40°F (4.5°C) 90°F (32°C) 62°F (16.5°C)
Fresh Air Level AI 46 0 CFM 20000 CFM N/A
Unoccupied Cool Setpoint AV 45 54°F (12°C) 100°F (37.5) 80°F (26.5°C)
Heating Setpoint Limit AV 48 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 49 54°F (12°C) 100°F (37.5) 54°F (12°C)
Heating Lockout Temperature AV 50 -15°F (-26°C) 120°F (49°C) 120°F (49°C)
Cooling Lockout Temperature AV 51 -40°F (-40°C) 95°F (35°C) -40°F (-40°C)
Deadband AV 52 2°F (1°C) 4°F (2°C) 2°F (1°C)
Password Value AV 59 0 1000 0
Power-up Delay AV 60 10 sec 120 sec 10 sec
Unoccupied Time AV 68 0.5 hrs 24.0. hrs 0.5 hrs
CO2 Level AI 69 0 PPM 2000 PPM N/A
Fresh Air Max Range AV 76 0 CFM 20000 CFM N/A
Economizer Changeover Setpoint AV 77 14°F (-10°C) 70°F (21°C) 55°F (13°C)
Economizer Minimum Position AV 78 0% 100% 0%
Mixed Air Setpoint AV 80 50°F (10°C) 90°F (32°C) 55°F (13°C)
Economizer Max Position AV 81 0% 100% N/A
High Balance Point AV 82 34°F (1°C) 90°F (32°C) 90°F (32°C)
Discharge High Limit Setpoint AV 82 70°F (21°C) 150°F (65°C) 120°F (49°C)
Discharge Low Limit Setpoint AV 83 35°F (2C) 65°F(19C) 65°F (7°C)
Low Balance Point AV 83 -40°F (-40°C) 30°F (-1°C) -12°F (-24°C)
Dehumidification RH Setpoint AV 89 30% 95% 50%
Dehumidification RH Setpoint AV 89 20% 100% 50%