EasyManuals Logo

Viconics VT76 Series User Manual

Viconics VT76 Series
29 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
14
Object name
Object Type
and instance
Under range
value
Over range
value
Default value
Dehumidification Hysterisys AV 90 2% 20% 5%
Dehumidification Low OA Lockout AV 91 -40°F (-40°C) 122°F (50°C) 32°F (0°C)
Humidification RH Setpoint AV 95 10% 90% 50%
Minimum Supply Heat Setpoint AV 95 50°F(10°C) 72°F(20°C) 64°F(18°C)
Eff (Effective) Reset
Humidification RH Spt (Setpoint)
AV 96 0% 100% N/A
Supply Heat Lockout
Temperature
AV 96 -15°F(-26°C) 120°F(49°C) 32°F(0°C)
Humidification High Limit Spt
(Setpoint)
AV 97 50% 90% 85%
Supply PI Heat Demand AV 97 0% 100% N/A
Low RH Setpoint AV 98 10% 90% 20%
Minimum Fresh Air AV 98 0 CFM 20000 CFM N/A
Low Temp Reset RH Setpoint AV 99 -40°F (-40°C) 15°F (-9.5°C) -20°F (-29°C)
Maximum Fresh Air AV 99 0 CFM 20000 CFM N/A
High Temp Reset RH Setpoint AV 100 20°F (-6.5°C) 55°F (13°C) 32°F (0.0°C)
Minimum CO2 Level AV 100 0 PPM 2000 PPM 800 PPM
Humidifier Output AV 101 0% 100% N/A
Maximum CO2 Level AV 101 0 PPM 2000 PPM 1200 PPM