15
List of Property Enumeration Sets for BI and BV objects
Object Name
Object Type and
instance
Inactive_Text Active_Text
Default
value
Room Temp Override BV 8 Normal Override Normal
Outdoor Temp Override BV 10 Normal Override Normal
Room Humidity Override BV 13 Normal Override Normal
AUX BI 24 Off On Off
BI 23
G Fan BI 25 Off On Off
Y1 Cool BI 26 Off On Off
Y2 Cool BI 27 Off On Off
W1 Heat BI 28 Off On Off
W2 Heat BI 29 Off On Off
Reversing Valve BI 30 Off On Off
DI 1 Status BI 31 Not Activated Activated Not Activated
DI 2 Status BI 32 Not Activated Activated Not Activated
Local Motion BI 33 No Motion Motion No Motion
Frost Alarm BI 36 Off On Off
Clock Alarm BI 37 Off On Off
Filter Alarm BI 38 Off On Off
Service Alarm BI 39 Off On Off
Fan Lock Alarm BI 40 Off On Off
Temperature Scale BV 47 °C °F °F
Frost Protection BV 55 Off On Off
Aux Contact BV 56 N.O. N.C. N.O.
Menu Scroll BV 57 No Scroll Scroll Active Scroll Active