10.2. Phase rotation warning
The AC supply, either Generator or Grid, to a three phase inverter/charger system needs to be in the correct rotation, also known
as sequence. If not, then the inverter/chargers will not accept the AC supply and remain in Inverter mode.
The Phase rotation warning will be raised in such case. To resolve the issue, change the wiring on the AC input: swap either one
of the phases, effectively changing the rotation from L3 → L2 → L1 to L1 → L2 → L3. Or reprogram the Multis and modify the
phase assigned to match the wiring.
On the GX device itself, the warning will popup as a notification on the GUI:
Also, it is visible in the menus:
On the VRM Portal, it is visible in the VE.Bus Alarms & warnings widget on the Advanced page and will be listed in the Alarm Log
on VRM. Furthermore, an email is sent; using the VRM Alarm Monitoring system.
Color Control GX Manual
Page 55 VE.Bus Inverter/charger monitoring

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Victron energy Cerbo-S GX and is the answer not in the manual?

Victron energy Cerbo-S GX Specifications

General IconGeneral
Input Voltage9 - 70 VDC
VE.Direct ports2
VE.Can ports1
Ethernet port1
USB ports2
WiFiYes
BluetoothYes
SD Card SlotYes
EnclosurePlastic
RS485 Ports1
ConnectivityEthernet, WiFi, Bluetooth
Humidity95%, non-condensing
Communication PortsVE.Direct, VE.Can, Ethernet, USB, WiFi, Bluetooth
GX Device CompatibilityCompatible with all GX devices
Remote MonitoringYes, via VRM
Firmware UpdatesYes
Operating Temperature-20 to +60 °C
Storage Temperature-40°C to +85°C

Related product manuals