What to do if the alarm LED flashes on my Victron Energy Inverter?
- JjeremysandovalAug 11, 2025
If the alarm LED is flashing, there could be several reasons: * The DC input voltage might be low: Charge the battery or check the battery connections. * The ambient temperature might be too high: Place the inverter in a cool and well-ventilated room, or reduce the load. * The load on the inverter might be higher than the nominal load: Reduce the load. * Voltage ripple on the DC input exceeds 1.25Vrms: Check the battery cables and terminals. Check the battery capacity; increase if necessary.