5
Pumps without switching input
LN
L
N
N PE
NL
L
D
C
A
B
A
Heating circuit pump
B Plug to EM-P1 extension
C
Contactor
D
Separate power supply (observe
manufacturer's instructions)
Specification for switching the con-
tactor:
Rated voltage 230 V~
Rated current 1 A
Recommended
connecting cable
H05VV-F3G
0.75 mm
2
or
H05RN-F3G
0.75 mm
2
Connecting the heating circuit pump
(cont.)
5831394