What should I do if pumps connected at the Viessmann Control Unit are not running?
- MMary ClementsSep 13, 2025
To troubleshoot pumps not running on your Viessmann Control Unit, check the operating voltage, including the mains isolator, power cable, plug, ON/OFF switch, and fuse F1 (6.3 A slow). If the fuse is faulty: 1. Pull out all 230 V plugs from the control unit (pumps, burner). 2. Replace the F1 fuse. 3. Reconnect all 230 V devices in sequence to identify the faulty device.