101
External heat generator
Parameter Code Delivered condition Commission-
ing
Maintenance/
service
"Enable external heat source" 7B00 0
"Priority ext. heat source/instant. heating
water heater"
7B01 1
"Dual mode temperature external heat
source"
7B02 100 (≙ 10 °C)
"Start threshold external heat source" 7B03 300 (≙ 30 min)
"Start delay external heat source" 7B04 30 min
"Min. flow temperature mixer external
heat source ON"
7B05 0
"Min. runtime external heat source" 7B06 20 min
"Run-on time external heat source" 7B07 10 min
"Max. excess flow temp external heat
source"
7B0B 0
"Enable external heat gen. for central
heating"
7B0C 1
"Enable external heat source for DHW
heating"
7B0D 0
"Dual mode heat pump operation" 7B0E 1
"Shutdown limit, heat pump dual mode" 7B0F –500 (≙ –50 °C)
"Enable min. temp. maintenance for ext.
HS"
7B10 0
"Enable boiler water temperature sen-
sor"
7B11 1
Commissioning/service reports
Control parameter report (cont.)
6199585
Appendix