EasyManua.ls Logo

Viessmann VITOCAL 100-S - Overview of Electrical Components

Viessmann VITOCAL 100-S
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
84
Measure Completed Comments
aS
Leak detection
The following leak detection processes are suitable for systems
with flammable refrigerants:
Leak detection with electronic refrigerant detectors:
Electronic refrigerant detectors may not have the required sensi-
tivity or may need to be calibrated to the relevant range. Carry
out the calibration in refrigerant-free surroundings.
The refrigerant detector must be suitable for the R32 refrigerant
to be detected.
The refrigerant detector must not contain any potential ignition
sources.
Calibrate the refrigerant detector to the refrigerant used. Set the
response threshold to < 3 g/a, suitable for R32.
Leak detection with liquid leak detectors:
Liquid leak detectors are suitable for use with most refrigerants.
!
Please note
Liquid leak detectors containing chlorine may react with
the refrigerant. This could result in corrosion.
Do not use liquid leak detectors that contain chlorine.
Measures to take if a leak in the refrigerant circuit occurs:
Immediately extinguish all open flames in the vicinity of the heat
pump.
Do not solder leaks in the refrigerant circuit.
aD
Extracting and evacuating refrigerant
Evacuating refrigerant: See chapter "Evacuating the refrigerant
lines and indoor unit"
aF
Topping up the refrigerant
Carry out work in accordance with chapter "Charging the refriger-
ant lines and indoor unit".
aG
Shutdown
Carry out the work in accordance with chapter "Final decommis-
sioning and disposal".
aH
Identification (labelling the heat pump)
If the heat pump has been taken out of use, affix a label to the
heat pump in a clearly visible position containing the following in-
formation with date and signature:
Outdoor unit works with flammable refrigerant R32.
System has been taken out of use.
Refrigerant has been extracted.
Outdoor unit may contain residual flammable refrigerant.
aJ
Recovering the refrigerant and compressor oil
Recovering compressor oil: See chapter "Disposing of the com-
pressor and compressor oil"
Overview of electrical components
Indoor unit:
See page 38 onwards.
Outdoor unit:
See page 48 onwards.
Maintenance
Checklist for maintenance work (cont.)
6199585
Maintenance

Related product manuals