EasyManua.ls Logo

Viessmann VITOCAL 100-S - Page 46

Viessmann VITOCAL 100-S
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
Terminals Function Explanation
With heat pump cascades
Power supply without on-site load disconnect:
Only connect the power-OFF signal to the lead heat
pump.
Power supply with on-site load disconnect: Con-
nect the power-OFF signal to all heat pumps.
For further information regarding power-OFF: See
chapter "Power supply".
X3.8
X3.9
Only for heat pumps with a cooling
function:
Frost stat
and/or
Contact humidistat 230 V~
Or jumper
For heat pumps without a cooling
function:
Jumper
Requires floating N/C contact:
Closed: Safety chain has continuity
Open: Safety chain interrupted; heat pump not opera-
tional
Breaking capacity 230 V~, 0.15 A
Connection:
Connected in series if both safety components are in-
stalled
Insert jumper if no safety components are instal-
led.
X40.L1 Heat pump control unit power supply:
Phase L1
X40.? Earth conductor terminal
X40.N Neutral conductor terminal
Power supply 230 V~
Indoor unit: Controller and sensor PCB (extra low voltage (ELV) connections)
Set the required parameters during commissioning:
See page 67 onwards.
Sensors
Plug Sensor Type
F0 Outside temperature sensor NTC 10 kΩ
F4 Buffer temperature sensor NTC 10 kΩ
F6
(X25.5/X25.6)
Top cylinder temperature sensor NTC 10 kΩ
F7
(X25.7/X25.8)
Cylinder temperature sensor, bottom NTC 10 kΩ
F11 Contact humidistat 24 V
Or jumper
Note
System with heating water/coolant buffer cylinder:
If cooling is performed via several heating/cooling circuits, provide a contact
humidistat for each heating/cooling circuit.
Connect several contact humidistats in series.
If a 230 V~ contact humidistat (connection to X3.8/X3.9) is used for cooling,
insert a jumper, otherwise the heat pump will not start (message "CA Pro-
tectn device primry").
F12 Flow temperature sensor, heating circuit with mixer M2/HC2 NTC 10 kΩ
F13 System flow temperature sensor (downstream of the buffer cylinder and mix-
er for external heat generator)
NTC 10 kΩ
F14 Flow temperature sensor, cooling circuit (heating circuit without mixer A1/HC1
or separate cooling circuit SKK)
NTC 10 kΩ
Installation sequence
Electrical connection (cont.)
6199585
Installation

Related product manuals