Parameters for utilisation of power generated on site
Parameter Setting
"Photovoltaics" Ó
"Enable own energy consumption PV 7E00" "1"
"Threshold for electrical power 7E04" "0" to "300" (≙ 0 to 30 kW)
Enable required functions for utilisation of power generated on site
Parameter Setting
"Photovoltaics" Ó
"Enable own energy consumption for set DHW temperature 2
7E10"
"1"
"Enable own energy consumption for DHW heating 7E11" "1"
"Enable own energy consumption for heating water buffer
cyl. 7E12"
"1"
"Enable own energy consumption for heating 7E13" "1"
"Enable own energy consumption for cooling 7E15" "1"
"Enable own energy consumption for coolant buffer cylinder
7E16"
"1"
Specify the temperature differential to the selected set value for the chosen function
Parameter Setting
"Photovoltaics" Ó
"Raise set DHW cylinder temperature PV 7E21" "0" to "500" (≙ 0 to 50 K)
"Raise set heating water buffer cylinder temp PV 7E22" "0" to "400" (≙ 0 to 40 K)
"Raise set room temperature PV 7E23" "0" to "100" (≙ 0 to 10 K)
"Reduce set room temperature PV 7E25" "0" to "100" (≙ 0 to 10 K)
"Reduce set coolant buffer cylinder temperature PV 7E26" "0" to "100" (≙ 0 to 10 K)
Parameters for heat pump cascade
Parameters Setting
Lead heat pump Lag heat pump
"Compressor" Ó
"Enable use of compressor stage 5012" "0" to "15" "0" to "15"
"System definition" Ó
"System scheme 7000" "0" to "10" "11"
"Cascade control 700A" "2" "0"
"Use of heat pump in cascade 700C" — "0" to "15"
"Number of lag heat pumps 7029" "1" to "4" —