131
Electric booster heater
Parameter Code Delivered condition Commission-
ing
Maintenance/
service
"Enable instantaneous heating water
heater"
7900 1
"Enable electric heaters for DHW heat-
ing"
7901 0
"Enable instant. heating water heater for
central heating"
7902 0
"Start delay instantaneous heating water
heater"
7905 30 min
"Max. output instantaneous heating wa-
ter heater"
7907 3
"Output for instant. heating water heater
at power-OFF"
790A 0
"Dual mode temp. instant. heating water
heater"
790B 500 (≙ 50 °C)
Internal hydraulics
Parameter Code Delivered condition Commission-
ing
Maintenance/
service
Heat pump for drying a building 7300 0
Time program for screed drying 7303 0
Set flow temperature external demand, cool-
ing
730A Do not adjust.
Set flow temperature external demand,
heating
730C 500 (≙ 50 °C)
Start threshold 730E 300 (≙ 30 K x min)
Compressor performance at min. outside
temperature
730F 50 %
Compressor performance at max. outside
temperature
7310 20 %
Cycle rate heating circuit pumps 7319 0
Rated output secondary pump (PWM) 7343 100 %
Rated output heating circuit pump HC2 734A 60 %
Starting time high efficiency circulation
pump
7365 Do not adjust.
Screed program start day 7378 1
Screed program end day 7379 31
Primary source
Parameter Code Delivered condition Commission-
ing
Maintenance/
service
"Primary source ctrl strategy" 7401 Never adjust
Commissioning/service reports
Control parameter report (cont.)
5831412
Appendix