130
DHW
Parameter Code Delivered condition Commission-
ing
Maintenance/
service
Set DHW temperature 6000 500 (≙ 50 °C)
Min. DHW temperature 6005 100 (≙ 10 °C)
Max. DHW temperature 6006 600 (≙ 60 °C)
Hysteresis DHW temperature heat pump 6007 50 (≙ 5 K)
Hysteresis DHW temperature booster heat-
er
6008 100 (≙ 10 K)
Start optimisation for DHW heating 6009 0
Stop optimisation for DHW heating 600A 0
Set DHW temperature 2 600C 600 (≙ 60 °C)
Temperature rise per hour for DHW heating 600D 30 K/h
Max. runtime DHW heating in heating mode 6011 240 (≙ 24 min)
Max. interruption of DHW heating for central
heating
6012 90 (≙ 9 min)
Enable electric heaters for DHW heating 6015 0
Start attempts for DHW after high pressure
shutdown
6017 0
Shutdown hysteresis inst. heating water
heater
601E 10 (≙ 1 K)
Enable elec. heating/ext. HS for reheating
only
6040 0
Solar
Parameter Code Delivered condition Commission-
ing
Maintenance/
Service
"Type solar control unit" 7A00 0
Parameters for solar control module, type
SM1
C0xx These parameters will only be displayed if the solar
control module, type SM1, is connected to the heat
pump and "Type solar control unit" is set to "3".
For a description of the parameters, see installation
and service instructions for "solar control module, type
SM1".
Commissioning/service reports
Control parameter report (cont.)