Please file in Service Binder
5673 650 - 01 04/2015
Operating Instructions
VITOCROSSAL 300
With Vitotronic 200 KW6B Controls
Vitocrossal 300
CU3A Series 26 to 57
Floor mounted, gas-fired condensing boiler with MatriX gas burner and Lambda Pro control
For operation with natural gas and liquid propane gas
Heating input 19 to 199 MBH
5.6 to 58 kW
Read and save these instructions
for future reference.
Product may not be exactly as shown
IMPORTANT
H
Do not store or use gasoline or other
ammable liquids in the vicinity of this
or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliances.
Do not touch any electrical switches,
do not use any phone in your building.
Immediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
If you cannot reach your gas supplier,
call the re department.
Installation and service must be
performed by a quali ed installer,
service agency or the gas supplier.
If the information in this manual is not followed
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
WARNING
Improper installation, adjustment, and/
or operation could cause carbon monoxide
poisoning resulting in injury or loss of life.
This product must be installed and serviced
by a professional service technician who is
experienced and qualified in hot water boiler
installation and gas combustion.
WARNING

Table of Contents

Other manuals for Viessmann VITOCROSSAL 300

Questions and Answers

  • J
    Jeremy HaneySep 19, 2025
    What causes the air pressure switch to not report air pressure and the fan to not run on a Viessmann Boiler?
    • T
      Timothy FitzgeraldSep 22, 2025
      If the air pressure switch is not reporting any air pressure and the fan is not running on your Viessmann Boiler, it could be because the air pressure switch is faulty, incorrectly connected, or incorrectly set. Replace the air pressure switch, and connect or set it correctly.
  • L
    Lori LawsonAug 25, 2025
    What to do if the gas pressure switch reports no gas pressure in my Viessmann VITOCROSSAL 300 Boiler?
    • L
      lisa59Aug 25, 2025
      If the gas pressure switch in your Viessmann Boiler reports no gas pressure, the gas shut-off valve may be closed or the gas pressure switch may be faulty. Open the gas shut-off valve and check the gas flow pressure. If necessary, clean the gas filter.
  • T
    Teresa RomeroAug 25, 2025
    Why does the air pressure switch switch off during operation in my Viessmann Boiler?
    • M
      mwheelerAug 26, 2025
      If the air pressure switch switches off during operation in your Viessmann Boiler, it might be due to flue gas back pressure or backed-up condensate. Remove the flue gas back pressure, check for backed-up condensate, and reset the burner control unit.
  • M
    Mrs. Mariah Wilson MDAug 27, 2025
    How to reset the on hold program on a Viessmann Boiler?
    • M
      Michael MorganAug 27, 2025
      If your Viessmann Boiler is in the on hold program, it could be due to a lack of gas at the VPS gas pressure switch or because the safety chain is not closed. Reset it by holding down the reset button until '9' flashes.
  • J
    John LeeSep 23, 2025
    Why is fan pressure produced during the air pressure switch idle state check on my Viessmann VITOCROSSAL 300 Boiler?
    • T
      tracymartinezSep 23, 2025
      If fan pressure is produced during the air pressure switch idle state check on your Viessmann Boiler, wind influence on the fan could be the cause. Check the flue draught (chimney).
  • L
    Linda MasonNov 27, 2025
    What to do if my Viessmann VITOCROSSAL 300 Boiler rooms are too cold?
    • S
      samanthajohnsonNov 27, 2025
      If your rooms are too cold, several issues could be the cause. First, ensure the heating system is switched ON via the ON/OFF switch and the mains isolator. Also, check the MCB in the power distribution board. If the issue persists, the control unit or remote control might be incorrectly adjusted. Ensure central heating is enabled and check the operating program, room temperature, time, time program for central heating, and the heating curve settings. Another cause might be that the DHW tank is being heated. Wait until the DHW tank has been heated up, consider reducing the DHW draw-off rate, or temporarily reduce the standard DHW temperature. Also, check the fuel reserves. With LPG, re-order if required. With natural gas, open the gas shut-off valve and consult your gas supply utility if n...
  • B
    Brandi MooreSep 12, 2025
    What does fault code 91 mean on a Viessmann Boiler?
    • L
      Lisa BanksSep 12, 2025
      If your Viessmann Boiler displays fault code 91, it indicates a short circuit in temperature sensor aÖ. You should check sensor aÖ on the solar control module.
  • P
    pwyattSep 12, 2025
    What does fault code 93 mean on a Viessmann VITOCROSSAL 300?
    • P
      patrick70Sep 12, 2025
      If your Viessmann Boiler displays fault code 93, it indicates a short circuit in the cylinder temperature sensor. You should check the temperature sensor at connection S3 to Vitosolic 100.
  • L
    Logan MarshallSep 4, 2025
    How do I fix fault code 58 on my Viessmann Boiler?
    • J
      joseph36Sep 4, 2025
      If your Viessmann Boiler displays fault code 58, it means there is a lead break in the cylinder temperature sensor. You should check the sensors.
  • M
    Melissa MccormickSep 2, 2025
    Why is my Viessmann Boiler showing fault code 38?
    • D
      Dana RamirezSep 2, 2025
      If your Viessmann Boiler displays fault code 38, it indicates a lead break in the boiler water temperature sensor. You should check the boiler water temperature sensor.

Summary

Safety

Safety, Installation, and Warranty Requirements

Essential guidelines for safe installation, operation, and warranty adherence.

Carbon Monoxide and Ventilation Safety

Details risks of carbon monoxide and importance of proper ventilation.

Controls

Operation

System Start-up, Shutdown, and Operation

Step-by-step guide for initiating, stopping, and operating the heating system.

Central Heating Control Settings

Configuration of room temperature, operating programs, and time schedules.

System Scanning and Diagnostics

Troubleshooting

Diagnosing Room Temperature Issues

Identifying causes and remedies for cold or overly hot rooms.

Maintenance and Servicing

Viessmann VITOCROSSAL 300 Specifications

General IconGeneral
ModelVITOCROSSAL 300
CategoryBoiler
Boiler typeCondensing Boiler
Heat Exchanger MaterialStainless Steel
Warranty2 years
EfficiencyUp to 98%
ControlVitotronic control system
Fuel TypeNatural Gas
Standard efficiency98%