Protection IP 30 to EN 60529;
safeguard through appro-
priate design and instal-
lation
Permissible ambient temperature
– during operation 0 to +40 °C
– during storage and transport -20 to +65 °C
Radio clock receiver
Part no. 7450 56 3
For receiving the DCF 77 time signal (location: Mainflingen near
Frankfurt/Main).
Radio control led setting of time and date.
Install on an outsi de wal l, facing the transmitter. The reception
may be reduced by metallic elements in the bui lding structure, e.g.
steel reinforced concrete, neighbouring buildings and sources of
electro-magnetic interference, e.g. HV and public transport lines.
Connection:
&
2-core lead, length up to 35 m with a cross-section of 1.5 mm
2
(copper)
&
Never route this lead immediately next to 230/400 V cables.
Vitocom 100, type FA1
Part no. 7178 18 8
KM BUS user
&
For remote reporting, remote monitoring and scanning of faults
via the telephone system
&
For remote control of heating systems via the telephone system
Configuration:
&
Telephone operating wi th the dual‐ tone multi‐ frequency (DTMF)
method
&
D1/D2/E‐Plus/O
2
mobile phones
&
Configuration tool (software for PC)
Fault messages are transmitted to the following communica-
tion services via the telephone system:
&
Fax
&
D1/D2 mobile phone
Standard delivery:
&
Vitocom 100
&
Power s upply cable (2.0 m long)
&
Connecting ca ble wi th RJ11 plug for telephone socket (3.0 m
long)
&
Adaptor RJ11/TAE6N
&
KM BUS cable with plug aVG (3.0 m long)
For accessories and further details, see the Viessmann technical
guide "Communication systems"
On‐site requirements:
&
RJ11 socket or
&
TAE socket, coding "6N"
Specification
Rated voltage: 230 V ~
Rated frequency: 50 Hz
Rated current : 15 mA
Safety class: II
Protection: IP 20 to EN 60529;
safeguard through appropri-
ate design and install ation
Function: Type 1B to EN 60 730‐ 1
Permissible ambient temperature
– during operation: 0 to +40 °C
Installation in living spaces
or boiler rooms (standard
ambient conditions)
– during storage and transport: ‐20 to +65 °C
Approval: CTR 21
Vitocom 300, type FA3, FE1 and FI1
&
Type FA3
Part no. 7143 428
&
Type FE1
Part no. 7143 430
&
Type FI1
Part no. 7143 429
In conjunction with a Vitodata 300:
&
For remote reporting, remote monitoring and scanning of faults
and/or data points via the internet
&
For remote switching, remote setting of parameters and codes
for heating systems via the internet
5822 335-1 GB