Rated heating output kW 150 200 250 310 400 500 620
Flue gas parameters
*2
Temperature at boiler wa-
ter temp. 80 °C
■ At rated heating output °C 215
■ At partial load (60 %) °C 155
Product ID CE-0085BP0365
Efficiency η at
■ 100 % of the rated heat-
ing output (80/65 °C)
% 90.8 91.0 90.9 91.0 90.9 91.0 91.1
■ 30 % of the rated heat-
ing output (80/65 °C)
% 94.5 94.9 94.7 95.0 94.7 95.0 95.2
*2
Values for sizing the flue system to EN 13384 relative to 13 % CO
2
for fuel oil EL
and 10 % CO
2
for natural gas.