ENGLISH - 29
00:20"and ends with the set-point for time step "23:40-
24:00".
- COPY DAY.
Copies the programme of a previously configured day into the
current day.
TEMP. LEVELS.
Displays and/or modifies the values of the temperature set-points
T1, T2, T3 for both heating and cooling programs.
8. RESET PROCEDURE.
Simultaneously press the four buttons (button A, button B, button
C, button D)
Confirm with “Yes” (button D).
All the programmable parameters revert to the default conditions (first
power-up): the clock is reset to zero, all user programs are deleted,
the 3 temperature set-points for automatic operation revert to their
default values).
9. CHARACTERISTICS.
Supply voltage:
- 16575: 120-230 V~ 50-60 Hz
- 16576: 3 V d.c. with 2 AA LR6 1.5 batteries (not included)
Average absorption: 1 VA
Front controls: “Esc”/“Mod”/“No”, “”, “”, “Set/ok/Yes
Clock backup battery duration:
- 16575-16575.B: about 10 days, with type CR2032 battery
• Output:
- 16575: 6(2) A 230 V~ change-over relay output
- 16576: 5(2) A 250 V~ change-over relay output
Type of regulation: ON/OFF
Temperature sampling frequency:
- every 5 s, with an average of the values acquired in 20 seconds
- instantaneous, in the event of a parameter being changed by the
user
Updating of display data: every 20 s
Ambient temperature display range: 0 °C +40 °C
Resolution of the reading: 0,1 °C
Resolution of the settings: 0,1 °C
Precision of the reading in heating mode:
- ≤ ±0,5 °C between +15 °C and +25 °C
- ≤ ±0,8 °C at the temperature extremes