Speed control range (open-loop) 1:100 of synchronous speed
Speed control range (closed-loop) 1:1,000 of synchronous speed
Speed accuracy (open-loop) 30–4,000 rpm: error ±8 rpm
Speed accuracy (closed-loop), depending on resolution of feedback device 0–6,000 rpm: error ±0.15 rpm
Torque control accuracy (speed feedback) max error ±5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor
Environment
Enclosure IP20
1)
/Type 1, IP21
2)
/Type 1, IP55/Type 12, IP66
Vibration test 1.0 g
Max. THVD 10%
Max. relative humidity 5%–93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Ambient temperature
3)
Max. 122 °F [50 °C] (24-hour average maximum 113 °F [45 °C])
1)
Only for
3.7 kW/5 HP (200–240 V),
7.5 kW/10 HP (400–480/500 V)
2)
As enclosure kit for
3.7 kW/5 HP (200–240 V),
7.5 kW/10 HP (400–480/500 V)
3)
Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation 32 °F [0 °C]
Minimum ambient temperature at reduced performance 14 °F [-10 °C]
Temperature during storage/transport -13 to + 149/158 °F [-25 to +65/70 °C]
Maximum altitude above sea level without derating 3,300 ft [1,000 m]
Derating for high altitude, see special conditions in the Design Guide.
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions in the Design Guide.