2-10 Vogt
®
VT Service Manual
Installation Instructions
FIGURE 2-11B
KeepRite VT100, 200/230V Remote Air Cooled Condenser Wiring
Note: Fan cycling switch, FCC2 (Danfoss) for fan motor #2, is not factory set.
Switch must be set in the field before startup. Cut Out = 210 psi, Diff = 25 psi.
Use an accurate gage to set, not the scale on the pressure switch.