05TA
TUBE-ICE
®
MACHINE
(Includes model P118F/HE100)
Manual Part Number 12A4171M06
Revision 3
Service Manual
$50
00

Table of Contents

Questions and Answers

  • S
    Sara ReedAug 31, 2025
    How to troubleshoot high head pressure in my water-cooled Vogt Ice Maker?
    • D
      Dawn GarciaAug 31, 2025
      To troubleshoot high head pressure in your water-cooled Vogt Ice Maker, consider these possible causes: a misadjusted or defective water regulating valve, which you should adjust or replace. Insufficient water supply, so check the size of the water line and pump output at the condenser. The cooling tower may need maintenance, so check the cooling tower fan belt and tighten or replace it as needed. Non-condensables (usually air) in the system; check refrigerant tables for correct pressure/temperature relation. A fouled (dirty) condenser; follow the diagnostic procedure outlined on page 7-3, Section 7, and clean the condenser per instructions under Condenser Cleaning.
  • T
    Tiffany NelsonSep 4, 2025
    What causes high head pressure in my air-cooled Vogt TUBE-ICE 05TA?
    • O
      ostevensSep 4, 2025
      High head pressure in your air-cooled Vogt Ice Maker can be caused by several factors. The condenser fan(s) may not be running due to a defective motor, fan control switch, fan contactor, or a tripped circuit breaker in the control panel (CB2). Replace any defective parts and check the condenser fan disconnect for a thrown switch or blown fuse. A dirty condenser restricting airflow can also cause this issue, so visually inspect the condenser and clean it as necessary. Additionally, non-condensables (usually air) in the system can be the cause. Follow the same procedure as specified for removing non-condensables from a water-cooled machine, but also evacuate the air-cooled condenser.
  • B
    Brian JonesSep 8, 2025
    What causes a low compressor oil level in my Vogt Ice Maker?
    • R
      ricky55Sep 8, 2025
      A low compressor oil level in your Vogt Ice Maker can be attributed to several factors. The oil separator may not be returning oil, so check the oil separator float and oil return stop valve (70) and line for any restrictions. Repeated short cycling, where refrigerant carries oil out of the compressor, is another cause, usually resulting from freeze-up, low refrigerant charge, low head pressure, a faulty timer, a faulty pressure switch, or a clogged expansion valve. Worn piston rings can also lead to low oil levels. Replacing the compressor is the best solution.
  • S
    Steven Dougherty MDNov 12, 2025
    What to do if my Vogt TUBE-ICE 05TA Ice Maker won't run?
    • M
      Matthew BaileyNov 12, 2025
      If your Vogt Ice Maker won't run, several issues could be the cause. First, check the electrical fused disconnect or circuit breaker supplying power to the machine. If power has been off, ensure the compressor crankcase heater is energized and warm, with no liquid refrigerant in the crankcase before starting. Then, push the "Start" button to begin a thawing cycle. Alternatively, the compressor motor overload (CMS-OL) may have tripped; inspect all motor contactor and compressor terminals for loose connections. Also, check the amperage, power supply, and head pressure. Another potential cause is a burnt-out 2.5 amp control circuit fuse (FU-I or FU-2) in the control panel. In this case, inspect the compressor crankcase heater, relay coils, contactors, starters, solenoid valves, and thawing ti...
  • F
    frosarioNov 16, 2025
    Why is my Vogt TUBE-ICE 05TA producing low ice capacity?
    • L
      Lisa ThomasNov 16, 2025
      If your Vogt Ice Maker has a low ice capacity, there are several potential causes. You may have a low refrigerant charge, so check for and repair any leaks, then add refrigerant. There might be a restriction in the liquid line, so inspect for partially closed valves or obstructions at the drier, strainer, solenoid valve, or expansion valve. Another possibility is that the float switch is stuck or has failed in the open position; ensure the float switch is opening and closing and that the “A1” valve is getting power. A leaking thawing gas solenoid valve (18) during the freeze cycle could also be the reason; verify that the manual opening stem is in the automatic position and check for valve leakage. Additionally, water distributors at the top of the freezer may be clogged, so remove the fre...
  • C
    Cynthia HorneNov 19, 2025
    What to do if my Vogt Ice Maker freezes up because ice fails to discharge?
    • A
      anthony81Nov 19, 2025
      If your Vogt Ice Maker freezes up because ice fails to discharge, several factors could be responsible. Insufficient heat for thawing, caused by low condensing pressure, non-condensables in the system, low refrigerant charge, or a thaw gas pressure switch adjusted too low, might be the issue. Ensure the head pressure is maintained at approximately 210 PSIG for R-22 or 250 PSIG for R-404a, correlating to 105 oF (37.8 C), using a water regulating valve (water-cooled units) or a fan cycling switch (air-cooled units). If non-condensables are present, the saturated temperature won't match the pressure reading at the receiver. The refrigerant level in the receiver should be near the operating mark at the end of a freezing cycle. Another cause could be a thawing time that is too short. Check the ...
  • A
    alicia24Nov 23, 2025
    Why is the ice quality poor in my Vogt Ice Maker?
    • A
      andrewwilliamsNov 24, 2025
      Poor ice quality in your Vogt Ice Maker can stem from several causes. An excessive concentration of solids in the water tank, often indicated by mineral deposits, may be the problem. Perform a cleaning procedure, remove the freezer cover, and clean the water distributors. Adjust continuous blowdown. Insufficient water supply, shown by a low tank level, could also be the cause. Check water pressure (30 PSIG minimum recommended) and for water line restrictions, partially closed valves, or a defective make-up water float valve. The water pump rotation might be incorrect. Check the rotation against the arrow on the pump housing and reverse two wires at the motor if needed. A low refrigerant charge can also lead to poor ice quality. Check the refrigerant level mark on the receiver. Insufficient...
  • J
    Jennifer LongNov 27, 2025
    Why does my Vogt TUBE-ICE 05TA Ice Maker freeze up due to an extended freeze period?
    • S
      Stephanie AndersonNov 27, 2025
      If your Vogt Ice Maker is freezing up due to an extended freeze period, several factors could be contributing. The freezer pressure switch setting may be too low; if so, adjust it or replace it if defective. The water tank drain valve (39) might be open or leaking, or the make-up water float valve (12) could be stuck open; in this case, close the valve, repair, or replace as necessary. Another potential cause is the thawing gas solenoid valve (18) leaking through during the freeze cycle; check the manual opening stem to ensure it is in the automatic position (stem screwed out), check for leakage through the valve, and close the stop valve (90) at the receiver to confirm leakage. Repair or replace the valve if needed. The float switch could be stuck or failed in the closed position; check t...

Vogt TUBE-ICE 05TA Specifications

General IconGeneral
TypeTube Ice Machine
Ice Production Capacity5 tons/day
RefrigerantR404A
Power Supply380V/3Ph/50Hz
DimensionsVaries depending on configuration; consult manufacturer
Ice ShapeHollow Cylinder