AC output mode
*This setting is only
available when the inverter
is in standby mode (Switch
off).
Single: This inverter is used
in single phase application.
Parallel: This inverter is operated
in parallel system.
When the inverter is operated in 3-phase application, set up
inverter to be operated in specific phase.
Low DC cut-off voltage:
If battery power is only
power source available,
inverter will shut down.
If PV energy and
battery power are
available, inverter will
charge battery without
AC output.
If PV energy, battery
power and utility are all
available, inverter will
transfer to line mode
and provide output
power to loads.
If self-defined is selected in
program 5, this program can be
set up. Setting range is from
42.0V to 48.0V. Increment of
each click is 0.1V. Low DC cut-off
voltage will be fixed to setting
value no matter what percentage
of load is connected.
Battery equalization disable
(default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
Battery equalization voltage
Setting range is from 48.0V to
61.0V. Increment of each click is
0.1V.