SPECIFICATIONS
Meter type: 3Phase-4-conductor meter
Measurement: Currently infed and discharged power pursuant to IEC62053
Accuracy class Class A (2%) pursuant to EN50470-1
Reference current Iref: 5 A
Threshold current Imax: 80 A
Start-up current Ist 20mA
Reference voltage Un: 230 V ± 20%
Reference frequency fn: 50 Hz
Meter constant: 1600imp/kWh
Voltage resistance: 4 kV, 50 Hz, 1 min
LCD display: 6 pre-decimal-, 2 post-decimal digits
Clamp Ø: 7 clamps, each 6.5 mm (60 A);
4 clamps for communication interfaces, 2 mm each
Outputs: RS-485 interface; S0-interface; visual impulse output
Weight: 290 g
Protection class: II
Protection type (casing): IP 51
Power consumption: 1.2 Watt
Connection type: Direct measurement
Temperature range: -25°C +70°C
Air humidity: <90%
Burst test: 4kV
Meter use: Indoors