EasyManua.ls Logo

WaterGroup Econoflo EFT30 - System Start-Up

Default Icon
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System Start-Up
1. Plug the power transformer into an ap-
proved power source. Connect the power
cord to the valve.
2. When power is supplied to the control, the
screen will display “WAITING PLEASE”
while it finds the service position.
3. Manually step the valve past the BRINE
position to the BACKWASH position. If
screen is locked, the screen will display
PRESS SETTINGS 3S TO UNLOCK. Fol-
low the instructions and press SETTINGS
for 3 seconds to unlock. Press and hold
the MANUL REGEN. Key for 3 seconds.
Press any key to skip the BRINE cycle.
4. Once in the BACKWASH cycle, open the
inlet on the bypass valve slowly and allow
water to enter the unit. Allow all air to es-
cape from the unit before turning the by-
pass fully open. Then allow water to run
to drain for 3-4 minutes or until all media
fines are washed out of the softener indi-
cated by clear water in the drain hose.
5. Press any button to advance to the RINSE
position. Check the drain line flow. Allow
the water to run for 3-4 minutes or until
the water is clear.
6. Press any button to advance to the REFILL
position. Check that the valve is filling wa-
ter into the brine tank. Allow the valve to
refill for the full amount of time as dis-
played on the screen to insure a proper
brine solution for the next regeneration.
7. The valve will automatically advance to the
SERVICE position. Open the outlet valve
on the bypass, then open the nearest
treated water faucet and allow the water
to run until clear, close the tap and replace
the faucet screen.
8. Add salt into the cabinet / brine tank.
9. Program unit.
Key Pad Configuration
Start-up Instructions
SETTINGS
Thisfunctionistoenterthebasicsetupinformationrequiredatthe
timeofinstallation.
MANUALREGEN
Thisbuttonhastwofunctions.Thefirstistoinitiateanimmediateor
delayedmanualregeneration.Thesecondiswhileinprogramming
mode,pressingthiskeyallowstheusertochangethevalueofea
ch
setting.
DOWN/UP
Increaseorde
creasethevalueofthesettingswhileintheprogram
mingmode.
8