Setup, Chapter 4
20
WATLOW Series 945 User's Manual
Operation
Operation Menu
Use this page as a master copy for your Series 945 Operation parameters.
Do not enter any values here; make photocopies instead.
Table 3 -
Operation Menu
Prompts and
Descriptions.
Parameters Value Range Factory Default Appears If:
Set Point 1 or rL to rH 75°F
Remote Set Point 1
SP2 rL to rH Primary set point. Ot1 = Ot2, Pb1 = 0
Pb1 If dFL = US:
0 - 999°F/0 - 555°C/0 - 999U 25°F/2.5°F
0 - 99.9°F/0 - 55.5°C/0 - 99.9U
0=ON/OFF control. HYS1 =swtch. diff.
If dFL = SI:
0 to 999.9% of span 3%/.3%
Pb2 Same as Pb1. 0°F Ot2 = ht or CL
Ot2 Ot1
rE1/It1 If dFL = US: 0.00 to 9.99 repeats/min. 0.00 rpt/min. Pb1 0
0.00 = No Reset.
If dFL = SI: 00.1 to 99.9 min./repeat 0.00
rE2/It2 Same as rE1/It1. 0.00 rpt/min. Pb2 0, Ot2 Ot1
Ot2 = ht or CL
rA1/dE1 0.00 to 9.99 min. 0.00 min. Pb1 0
0.00 = No Rate.
rA2/dE2 Same as rA1/dE1. 0.00 min. Pb2 0, Ot2 Ot1
Ot2 = ht or CL
Ct1 1 to 60 seconds 5 seconds Pb1 0, Output1 420
Ct2 1 to 60 seconds 5 seconds Pb2 0, Ot2 Ot1,
Ot2 = ht or CL
db ±0 - 99°F/±0 - 55°C/0 - 99U. 0 Ht/CL or CL/Ht
±0.0 - 9.9°F/0.0 - 5.5°C/0.0 - 9.9U
A1LO Deviation dE -999° to 0° -999° AL1 = Pr, dE
Process Pr rL to A1HI rL Unit has alarms
A1HI Deviation dE 0° to 999° 999° AL1 = Pr, dE
Process Pr A1LO to rH rH Unit has alarms
A2LO Deviation dE -999° to 0° -999 AL2 = Pr, dE
Process Pr rL to A2HI rL Unit has Alarm 2
A2HI Deviation dE 0° to 999° 999° AL2 = Pr, dE
Process Pr A2LO to rH rH Unit has Alarm 2
CAL ±180°F/±100°C/±180U 0
AUt 0-3 0 Ot1 = ht, L-r = L
L-r L or r L rsP = 0-5 or 420
Auto-Tune: Initiates auto-tune for Output 1. This parameter appears if Ot 1 =ht.
Range: 0 = off, 1 = slow, 2 = medium, 3 = fast Default: 0
Local-Remote: Selects a local or remote set point for the Series 945. This parameter
only appears if the LOC parameter = 0, 1 or 2, and rSP = 0-5 or 420. If L-r = r, the
remote set point will be displayed in place of the internal set point.
Range: L = Local operation r = remote operation Default: L