EasyManua.ls Logo

Watlow 945 Series - Specifications; Control Mode; Input; Primary Output (Heating or Cooling)

Watlow 945 Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
42
WATLOW Series 945 User's Manual
Specifications
Secondary Output (Heat, Cool or None)
Solid state relay, Form A, 0.5A @ 24VAC min., 264VAC
maximum, opto-isolated, zero cross switching. Off state
impedance is 20K minimum for 945A-XBXX-X000
units, and 31M for 945A-XKXX-X000 units.
Electromechanical relay, Form A, 6A @ 120/240VAC, 6A
@ 28VDC, 1/8 hp. @ 120VAC, 125VA @ 120VAC. Off
state impedance is 20K min. Typical relay life is
100,000 cycles.
Switched DC (Open collector), 500 min. load resis-
tance, 1K load, 9mA min., 22mA max., non-isolated.
Alarms
Electromechanical relay, Form A (N.O.) or B (N.C.), 6A
@ 120/240VAC, 6A @ 28VDC, 1/8 hp. @ 120VAC,
125VA @ 120VAC. Off state impedance is 20K min.
Typical relay life is 100,000 cycles.
Latching or non-latching.
Process or deviation.
Separate high and low values.
Alarm silencing (inhibit) on power up for Alarm 1.
Retransmit Output
4-20mA into a 600 maximum load, non-isolated.
0-5VDC into a 10K minimum load, non-isolated.
Retransmit of process or set point. User selectable range.
Accuracy
Calibration Accuracy & Sensor Conformity: ± 0.1% of
span, ± 1LSD, 77°F ± 5°F(25°C ±3°C) ambient & rated
line voltage ±10%.
Accuracy Span: 1000°F or 540°C minimum.
Temperature Stability: 0.1°F/°F (0.1°C/°C) change in
ambient.
Voltage Stability: ± 0.01% of span / % of rated line
voltage.
Communications
Serial data communications.
RS-422A or RS-423A (RS-232C compatible) or EIA-485.
ANSI X3.28 protocol, or XON/XOFF protocol.
Isolated.
Data logging.
#6 compression type screw terminals.
Agency Approvals
UL recognized, File #E43684, UL873.
CSA recognized, File # LR30586.
Terminals
#6 compression type screw terminals.
Power
120/240VAC +10%, -15%, 50/60Hz, ± 5%.
16VA maximum.
Data retention upon power failure via nonvolatile
memory.
Operating Environment
32 to 149°F/0 to 65°C.
0 to 90% RH, non-condensing.
Dimensions
Height: 3.8 in 97 mm
Width: 3.8 in 97 mm
Overall depth: 7.0 in 178 mm
Behind panel depth: 6.0 in 153 mm
Weight: 2.5 lb max. 0.4 kg
Control Mode
Single or dual set point, non-ramping.
Single input, dual outputs, dual alarms.
Optional retransmit of set point or process variable.
Control outputs: User selectable as: Heat, Heat/Heat,
Heat/Cool, Cool, Cool/Cool, Cool/Heat.
Outputs independent, or related via deadband for
Heat/Cool.
ON/OFF: Determined by the HYSX parameter for
Outputs 1 and 2.
Proportional band: 0 to 999°F/0 to 555°C/0 to 999 U
or 0 to 999.9% of span.
Reset: 0.00 to 9.99 repeats per minute.
Integral: 0 and 00.1 to 99.9 minutes per repeat.
Rate/Derivative: 0.00 to 9.99 minutes.
Cycle time: 1 to 60 seconds.
Dead band: ±99°F, ±99 units or ±55°C (±9.9°F, ±9.9
units or ±5.5°C for rtd.1 and process units)
Operator Interface
Membrane front panel.
Dual, four digit 0.56" (14 mm) LED displays.
MODE, AUTO/MANUAL, UP, and DOWN keys.
Input
Automatic cold junction compensation for thermocouple.
RTD input 2 or 3 wire, platinum, 100 ohm @ 0°C
software selectable, JIS curve #3916 (0.003916 //°C)
or DIN curve #3850(0.003850 //°C).
Sensor break protection de-energizes control outputs to
protect system or selectable bumpless transfer to
manual operation.
Grounded or ungrounded sensors.
°F,°C, or process variable units are user selectable.
Operating ranges user selectable.
J t/c: 32 to 1382°F or 0 to 750°C
K t/c: -328 to 2282°F or -200 to 1250°C
T t/c: -328 to 662°F or -200 to 350°C
N t/c: 32 to 2282°F or 0 to 1250°C
C t/c: 797 to 4200°F or 425 to2315 °C
PT 2 (Platinel 2) 32 to 2543°F or 0 to 1395°C
R t/c: 32 to 2642°F or 0 to 1450°C
S t/c: 32 to 2642°F or 0 to 1450°C
B t/c: 1598 to 3092°F or 870 to 1700°C
1° RTD: -328 to 1112°F or -200 to 600°C
0.1° RTD: -99.9 to 392.0°F or -99.9 to200.0°C
0-5VDC: -500 to 3500 units
4-20mA: -500 to 3500 units
Primary Output (Heating or Cooling)
Solid state relay, 0.5A @ 24VAC min., 264VAC max.
opto-isolated, zero cross switching. Off state impedance
is 20K min. for 952A-XBXX-X000 units, and 31M
for 945A-XKXX-X000 units.
Electromechanical relay, Form C, 6A @ 120/240VAC, 6A
@ 28VDC, 1/8 hp. @ 120VAC, 125VA @ 120VAC. Off
state impedance is 20K minimum. Typical relay life of
100,000 cycles.
Switched DC (Open collector), 500 min. load resis
tance, 1K load,9mA min., 22mA max., non-isolated.
4-20mA reverse or direct acting into a 600 maximum
load impedance,non-isolated.
0-5 VDC reverse or direct into a 1K minimum load
impedance, non-isolated.
(1359)