Setup, Chapter 4
18
WATLOW Series 945 User's Manual
Operation
Figure 32 -
The Operation Menu
 NOTE:
The upper display will
always return to the
process value after 1
minute without key
strokes.
Operation Menu
In the Operation menu, the 945 operates as a digital set point control.  All outputs
are turned OFF when set point is set to OFF.
= Parameter may not appear
depending on control configuration
= Only appears if your unit has communications.
See the Series 945 data communications
manual for more information.
M
Mode Key
75
SP2
Pb1
Pb2
rE1/It1
rE2/It2
rA1/dE1
rA2dE2
Ct1
Ct2
db
A1LO
A1HI
A2LO
A2HI
CAL
AUt
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
(    )
CLUP
(    )
[Control Set Point or
Remote Set Point ]
Set point 2
Proportional band 1
Proportional band 2
Reset 1/Inte
ral 1
Reset 2/Inte
ral 2
Rate 1/Derivative 1
Rate 2/Derivative 2
C
cle time 1
C
cle time 2
Dead band
Alarm 1low
Alarm 1 hi
h
Alarm 2 low
Alarm 2 hi
h
Calibration offset
Auto-tune
Control limit update
L - r
(    )
Local-remote
Operation Parameters
Set Point 1 or Remote Set Point 1:  Sets the operating set point for the control
outputs.  Appears if L-r = L, see Page 20.  If L-r = R, this parameter represents the
remote set point.  Range:  OFF / rL to rH         Default:  Dependent on input range
Set Point 2:  Sets the operating set point for Output 2 when control mode is ht/ht or
CL/CL.  Appears when Ot1 and Ot2 are the same, and functions as an ON/OFF
control.  Range:  rL to rH Default:  Same as primary set point.
Proportional Band:  Expressed in degrees, process units or % of span, within which
a controller proportioning function is active for Output 1 or 2.  When PbX = 0, it
functions as an ON/OFF control.  The switching differential is then determined by the
corresponding HYSX parameter. Pb1 is always visible.  Pb2 will not appear if your unit
does not have Output 2, Ot2 = no, or Ot2 is the same value as Ot1.  Also dependant
on the dFL parameter in the Calibration menu.
If dFL = US:  Range:  0 to 999°F/0 to 555°C/0 to 999 Units; 0.0 to 9.9°F/0.0 to 5.5°C/
0.0 to 9.9 Units Defaults: 
Pb1
 =  25°F/2.5°F
Pb2
 = 0
If dFL = SI:  Range:  0 to 999.9% of span Defaults:  
Pb1
 = 3.0%
Pb2
 = 0.0%
75
SP2
Pb1
Pb2