EasyManua.ls Logo

Watlow QPAC-01 - How to Install and Wire the QPAC, Chapter 2

Watlow QPAC-01
35 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Starting Out
14
QPAC User's Manual
How to Install and Wire the QPAC, Chapter 2
Circuit
Breakers
or
Disconnects
Contactors
If Required
Onboard,
factory
installed
semicon-
ductor
fuses
QPAC-01 50A
Heater
Load
L1 T2
T1
L2
Circuit
Breakers
or
Disconnects
Contactors
If Required
Onboard,
factory
installed
semicon-
ductor
fuses
QPAC-01 30A
Heater
Load
L1 T2
T1
L2
Figure 16 -
QPAC-01 Wiring
for 50A Units
Figure 15 -
QPAC-01 Wiring
for 30A Units
ç
CAUTION:
Check terminals for tightness before applying power and then recheck terminals
after one day of operation. Loose connections can damage the SCR.
QPAC-01 Power and Load Wiring
Wire QPAC-01
WARNING:
To avoid potential
electric shock and
other hazards, all
mounting and wiring
for the QPAC must
conform to the
National Electric
Code (NEC) and
other locally appli-
cable codes.
NOTE:
On 120Vac or
277Vac, L2 is neutral
and cannot be
broken.
NOTE:
A contactor is
required if a high
limit control is used.