EasyManua.ls Logo

Watlow Series 96 - Ordering Information

Watlow Series 96
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Active if output 4 is process (96 _
_- _ _ _ M -_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1622 w10.00 (1000)0.00 to 99.99
[4`10] Output Calibra-
tion 4, 10V
Enter the output
value in volts as
measured.
Active if output 4 is process (96 _
_- _ _ _ M -_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1621 w1.00 (100)0.00 to 99.99
[4``1] Output Calibra-
tion 4, 1V
Enter the output
value in volts as
measured.
Active if output 4 is process (96 _
_- _ _ _ M -_ _ _ _) and Calibra-
tion Lock (Lockout Menu) is not
set to [hide].
1620 w20.00 (2000)0.00 to 99.99
[4`20] Output Calibra-
tion 4, 20mA
Enter the output
value in milliamps
as measured.
Watlow Series 96 Calibration 11
Display Parameter Range Default Modbus Conditions for
(Modbus Value) Address Parameters to Appear
Read/Write
Ordering Information (1551)
Series 96
9 6
——
————
————
Microprocessor-based
1
/16 DIN with universal input 1.
Options include software, power supply,
input 2, four outputs and display color
Power Supply
A = 100-240Vı (ac/dc)
B = 24-28Vı (ac/dc)
Input 2
0 = None
1 = Event input & 0-5VÎ (dc)/
4-20mA (remote set point input)
Output 1
C = Switched dc/open collector
D = Electromechanical relay, Form C,
2A, without RC suppression
F = Universal Process, range selectable: 0-20mA,
4-20mA, 0-5VÎ (dc), 1-5VÎ (dc), 0-10VÎ (dc)
K = 0.5A solid-state relay without
RC suppression
Output 2
A = None
C = Switched dc output/open collector
D = Electromechanical relay, Form C, 2A, without RC suppression
F = Universal Process, range selectable: 0-20mA,
4-20mA, 0-5VÎ (dc), 1-5VÎ (dc), 0-10VÎ (dc)
K = 0.5A solid-state relay without
RC suppression
Output 3
A = None
D = Electromechanical relay, Form C, 2A, without RC suppression
Output 4
A = None
D = Electromechanical relay, Form C, 2A, without RC suppression
R = 232 Communications
U = 485 Communications
M = Universal Retransmit, range selectable: 0-20mA,
4-20mA, 0-5VÎ (dc), 1-5VÎ (dc), 0-10VÎ (dc)
Software/Preset Parameters
00 = Standard software
AA = Ramping
Display/Overlay
Upper/Lower
RR = Red/Red display GR = Green/Red display
RG = Red/Green display GG = Green/Green display

Related product manuals