Calibrating the Series 96
Warm up the unit (20 minutes). To enter a calibration menu, enter the Factory Page by holding
down the ˆ and keys for six seconds. Once in the Factory Page [Fcty] use the Up-arrow ¿ or
Down-arrow ¯ Key to select a menu. The last three menus on the Factory Page are Calibration 1
Menu [cin1], Calibration 2 Menu [cin2] and Process Output Calibration Menu [cout].
You can restore the original factory calibration with Restore Factory Calibration [`rSt]
(Calibration 1 Menu) or revert to the default parameter range selections with Default Settings
[dFLt] (Calibration 1 Menu).
Figure 3 – The Calibration Menus.
[CUSt] Custom Menu
[FctY]
Factory Page
[Fcty] Factory Page
[`rSt] Restore Factory Calibration
[dFLt] Default Settings
[tc50] Thermocouple Calibration, 50mV
[tc00] Thermocouple Calibration, 0mV
[tc32] Thermocouple Calibration, 32mV
[`gnd] Set Ground
[LEAd] Lead Resistance Calibration
[r`15] RTD Calibration, 15
[r380] RTD Calibration, 380
[A`0u] Process Calibration 1, 0V
[A10u] Process Calibration 1, 10V
[A`4A] Process Calibration 1, 4mA
[A20A] Process Calibration 1, 20mA
[Fcty] Factory Page
[b`0u] Process Calibration 2, 0V
[b10u] Process Calibration 2, 10V
[b4A`] Process Calibration 2, 4mA
[b20A] Process Calibration 2, 20mA
[Fcty] Factory Page
[1``4] Output Calibration 1, 4mA
[1`20] Output Calibration 1, 20mA
[1``1] Output Calibration 1, 1V
[1`10] Output Calibration 1, 10V
[2``4] Output Calibration 2, 4mA
[2`20] Output Calibration 2, 20mA
[2``1] Output Calibration 2, 1V
[2`10] Output Calibration 2, 10V
[4``4] Output Calibration 4, 4mA
[4`20] Output Calibration 4, 20mA
[4``1] Output Calibration 4, 1V
[4`10] Output Calibration 4, 10V
¿
[`LOC] Lockout Menu
[FctY]
[dIAg] Diagnostics Menu
[FctY]
[cin1] Calibration 1 Menu
[FctY]
[cin2] Calibration 2 Menu
[FctY]
[cout] Process Output Calibration Menu 1
[FctY]
¯
¿
¯