3. Remove and dispose of the cap with jumper wire attached.
4. Plug the Molex connector into the sequencing isolation valve’s connector.
5. When the Sequencing Isolation Valve is used, the Controller’s Auxiliary Delay setting
must be set to 120 seconds. Go into the Controller’s Main Menu → Advanced Setup →
Ancillary Device → Interlocks screen and set the Auxiliary Delay parameter to 120.
Figure 2-16: Intelocks Screen – Auxiliary Delay Parameter