IOM-T-294 2205 © 2022 tekmar
5
Use a Phillips screwdriver to remove
the two screws on the cover.
Pull the front cover towards you. The
top of the cover will pivot on a hinge.
Remove the cover by releasing the
pivot hooks.
Mount the enclosure to a wall using
#6 wood screws in the four mounting
holes. Use screw anchors if drilling
into masonry.
Use the 24 knock-outs to install
connecting conduits and cabling to
the control.
To install the cover, hook the top
of the cover to the enclosure, then
pivot the bottom to shut.
Use a Phillips screwdriver to fasten
the two bottom screws.
When choosing the location for the control, consider the following:
• Keep dry. Avoid potential leakage onto the control.
RH
90% to 104°F (40°C).
Non-condensing environment.
• Do not expose to operating temperatures beyond 32-104°F
(0-40°C)
• Provide adequate ventilation.
• Keep away from equipment, appliances or other sources of
electrical interference.
• Provide easy access for wiring, viewing, and adjusting the
display screen.
• Mount approximately 5 ft. (1.5 m) off the finished floor.
• Locate the control near pumps and/or zone valves if possible.
• Provide a solid backing to mount the enclosure to. For
example: plywood, studs, etc
• Use the conduit knockouts provided on the upper, lower,
back and sides of the enclosure.
Installation
Installation Location