EasyManua.ls Logo

WEG WECM - Page 17

WEG WECM
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.weg.net
WECM / Emerald eZA Manual | 17
10. Address table
R(01) – Single Register reading
R(03) – Multiple Register reading
Read / Write Function Address and Notes
R(01) Local/Remote Mode Read Register address:0x0000
0: Local;
1: Remote.
R(01) Relay State Read Register address: 0x0001
0: open
1: close
R(01) Read Fire mode flag Read Register address: 0x0002
0: out fire mode;
1: in fire mode
R(01) Read AC lose flag Read Register address: 0x0003
0: False
1: True
R(01) Read direction Read Register address: 0x0004
0: CW
1: CCW
R(01) Read Run/Stop Read Register address: 0x0005
0: Stop;
1: Run.
R(03) Read motor number Read Register address: 0x0000
R(03) Read firmware version of motor driver MCU Read Register address: 0x0001
R(03) Read software version of Mid-controller Read Register address: 0x0002
R(03) FCT Max Speed Read Register address: 0x0003
R(03) Current Max Speed Read Register address: 0x0004
R(03) Read motor Target speed Read Register address: 0x0005
R(03) Read motor actual speed Read Register address: 0x0006
R(03) Read DC bus voltage Read Register address: 0x0007
R(03) Read output current (motor) Read Register address: 0x0008
R(03) Read output voltage (motor) Read Register address: 0x0009
R(03) Read frequency (motor) Read Register address: 0x000A
R(03) Read IPM Temperature Read Register address: 0x000B
R(03) Read Error code Read Register address: 0x000C
Refer to Fault error code
R(03) Read multi register 0x01 + 0x03 + start address +
register number N + CRC
W(06) Modbus control enable Write Register address: 0x0000
0: disable
1: enable
W(06) Run/Stop Write Register address: 0x0001
0: Stop
1: Run
W(06) Write Max speed Write Register address: 0x0002
W(06) Write Target speed Write Register address: 0x0003