Polyol Ester (POE) Lubricants (continued):
lubricant because of its particular additives. ICI Emkarate RL 32S is an acceptable
alternative when the Mobil is not available. These POE lubricants must be used with
HFC refrigerants. Lubricants are packaged in specially designed, sealed containers.
Once opened, use the lubricant immediately. Properly dispose of any unused lubricant.
Evaporator Troubleshooting Chart:
Replace fuse(s). Check for
short circuits or overload
Defective timer or defrost
thermostat
Replace defective component.
Wait for completion of cycle.
Walk-in temperature too high.
Adjust thermal expansion valve.
System low on refrigerant
Locate and repair leak, recover,
evacuate and recharge.
Manually defrost coil. Check
defrost controls.
Ice accumulating on ceiling
around evaporator and/or on fan
guards, venturi, or blades.
Defrost duration is too long
Adjust defrost termination
thermostat (if adjustable).
Fan delay not delaying fans
after defrost period
Replace defective defrost
thermostat.
Defective defrost thermostat or
timer
Replace defective component.
Too many defrost cycles per
day
Reduce number of defrost
cycles per day.
Frost on coil after defrost cycle.
Coil temperature not getting
above freezing point during
Not enough defrost cycles per
day
Adjust timer for more defrost
cycles per day
Adjust timer for longer cycle,
check defrost thermostat
Defective timer or defrost
thermostat
Replace defective component.
Ice accumulating in drain pan.
Unit not pitched properly
Defective drain line heater
Defective timer or thermostat
Replace defective component.