WIRING
208 V, 208 V/240 V, 240V, and 480 V models may be wired for operation in the field for either 1-phase
or 3-phase [delta] power supplies by making line connections at the junction box located at the right,
rear of the unit as described on the wiring diagram. G60 models will have an additional box on the left
rear as it utilizes two connections. 380 V–415 V models can only be wired as 3-phase wye.
CONNECT/PLUG UNIT INTO DEDICATED AC LINE WITH APPROPRIATE
AMPERAGE/VOLTAGE AS SPECIFIED ON THE NAMEPLATE OF THE UNIT.
DO NOT IMMERSE OR LET THE UNIT STAND IN WATER.
DO NOT HOSE DOWN THE UNIT OR THE TABLE/COUNTER IF THE UNIT
IS ON THE TABLE/COUNTER.
KEEP AWAY FROM RUNNING WATER.
ELECTRICAL FIGURES
MODEL VOLTAGE TOTAL kW L1 L2 L3 N [wye] 1-phase
G13
208/240 6.8/9 14/18.7 28.1/32.5 14/18.7 32.5/37.5
380–415 10.7 [max] 14.8 [max] 14.8 [max] 14.8 [max] 0
480 9 9.4 16.2 9.4 18.7
G19
208 12 28.8 49.9 28.8 57.6
240 12 25 43.3 25 50
380–415 16.1 [max] 22.2 [max] 22.2 [max] 22.2 [max] 0
480 12 12.5 21.6 12.5 25
G23
208 15.9 48.3 51.3 35 76.9
240 16 41.7 44.4 30.4 66.6
380–415 16 [max] 15.8 [max] 31.6 [max] 19.1 [max] 14.5 [max]
480 16 20.9 22.2 15.2 33.3
G24
208 20.9 63.4 67.1 45.8 103.3
240 21 55 58.3 39.6 89.5
380–415 21 [max] 20.9 [max] 41.8 [max] 25 [max] 19.1 [max]
480 21 27.1 28.9 19.9 43.8
G601
208 31.8 [2 x 15.9] 48.31 51.31 351 76.91
240 32 [2 x 16] 41.71 44.41 30.41 66.61
380–415 32.4 [max, 2 x 16.2] 15.81 [max] 31.61 [max] 19.11 [max] 28.3 [max]
480 32 [2 x 16] 20.91 221 15.21 33.31
1This unit has two connections—amps are shown per connection [half of total for unit].