Westerbeke W-46 - BT Generator Internal Wiring; 3 Phase Twelve Wire Reconnectable Wiring; BT Generator Troubleshooting (3 Phase)

Westerbeke W-46
114 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BT
GENERATOR
INTERNAL
WIRING
3
PHASE
TWELVE
WIRE·RECONNECTABLE
r-------------.
I I
I ' A
EXCITER
STATOR
I
I I
I I
I
r-----~--------~-,u
,-------,
1
DsTATDR
I
I 1 I I
10
I 1 I C l
: :
EX'TER
:
ROTOR
FJElD
: S
I I I 6
I I
I I 2
I I
I I 4
I I
I I
_________
.J
-,.,
<.:1
·s
ffi
ca
"'
RED
BLUE
YELLOW
BT
GENERATOR
TROUBLESHOOTING/3
PHASE
GREEN
11
9
7
5
1
3
RESISTANCE
VAWES
A.
EXCITER
STATOR
(17.9
ohm)
B.
EXC~:t"ER
ROTOR
WINDINGS
a b c
(0.6
ohm)
_
C.
ROTATING
FIELD
(2.49
ohm)
D.
MAIN
STATOR
WINDINGS
(0.05
ohm}
AUXILIARY
WINDING
(1.2
ohm)
E.
VOLTAGE-REGULATOR
-
NOTE:
AC generator
troubleshooting
must
be
performed
with
the engine
operatin
at
60Hz,
F.
AUXILIARY
CIRCUIT
FUSE
FAULT
NO
AC
VOLTAGE
OUTPUT
AT
NO
LOAD.
RESIDUAL
VOLTAGE
PRODUCED
AT
NO
LOAD
15
20
VOLTS
AC.
LOW
AC
VOLTAGE
OUTPUT
AT,
NO
LOAD
60
·100
VAC.
HIGH
AC
OUTPUT
VOLTAGE
150
VAC
OR
HIGHER.
UNSTABLE
VOLTAGE
OUTPUT.
AC
VOLTAGE
DROP
UNDER
LOAD
60
·100
VOLTS
AC.
PROBABLE
CAUSE
1.
Short
or
open
in
the
main
stator
winding.
2.
Shorted
suppressor
on
exciter
rotor.
3.
Four
or
more
shorted
or
open
diodes
on
exciter
r.oto.r.
1.
Blown
6
AMP
fuse
auxiliary
circuit
AVR.
2.
Faulty
voltage
regulator
1.
Open
or
shorted
diodes
ln.
exciter
rotor
1
to
3
diodes.
2.
Shorted
exciter
rotor
winding.
1.
Faulty
voltage
regulator.
1.
STB
pod
on
regulator
needs
adjustment.
1.
Diode(s)
on
exciter
rotor
breaking
down
when
load
is
applied
(inductive)
1-3
diodes.
Engines & Generators
97
4.
Open
in
exciter
stator
winding.
5.
Open
in
rotating
field
winding.
3.
Shorted
or
open
main
stator
auxiliary
winding.
3.
Faulty
voltage
regulator.
1
•.
2.
Faulty
voltage
regulator.

Related product manuals