22
6614-2202
=Termination
T
R-36 485 
Slave unit Slave unit Slave unit
T
R-36 485
Slave unit Slave unit Slave unit
Max 0.3 metre
=Termination
T+
T–
T+T- T+T- AB
R+
R–
T+
T–
R– R+ R+T– T– B’ A’ BAT+T+ R–
2-wire termination
4-wire termination
RS-422/485 general advice
Termination recommendations
The RS-422/485 line must be terminated.In the TR-36,the termination is combined with 
fail-safe functionality.The termination is used to prevent undefined states when the bus is 
in tri-state condition.
…  Using 2-wire RS-485 both ends should be terminated.
…  Using 4-wire RS-485 both pairs shall be terminated at both ends.
…  Using 4-wire RS-422 it’s only necessary to terminate the receivers.
RS-422/485 connection pins can be differently named.For some equipment brands 
the T+ corresponds to A,but other brands might use some other naming convention.
If a unit does not work it can help to swap A and B.